Violation Detail
Standard Cited: 19100119 J04 IV Process safety management of highly hazardous chemicals.
Inspection Nr: 1069599.015
Citation: 02001
Citation Type: Repeat
Abatement Date: 01/27/2016 2
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 12/04/2015
Nr Instances: 8
Nr Exposed: 76
Related Event Code (REC):
Gravity: 5
Report ID: 0523900
Contest Date:
Final Order: 12/29/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/29/2015 | $7,000.00 | 01/27/2016 | Repeat | |
Penalty | Z: Issued | 12/04/2015 | $7,000.00 | 01/27/2016 | Repeat |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that was performed on process equipment wherein the documentation identified the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test: (a) E-II Building; The employer did not provide documentation to identify the date of the test/inspection, the name of the person who performed the test/inspection, the serial number or other identifier of the equipment on which the test/inspection was performed, a description of the test/inspection, and the results of the test/inspection up to and including exercising the final element of the control for such items as but not limited to: (1) Liquid Molecular Sieve - Valve V-018 (2) Delta-T Molecular Sieve - Pressure relief valves (V-064, V-184) (3) E-4 Thin Film Evaporator - Level Switch I-141, vessel E-106, and pressure relief valves (V-059 and V-233) (4) E-23 Thin Film Evaporator - Vessel E-260 (5) F-2 Fractionation Still - Pressure relief valve (V-017) (6) F-3 Fractionation Still - Pressure relief valve (V-045) (7) R-1 Dry-Film Reactor - Pressure relief valves (V-057, V-058, V-059, V-060, V-132, V-045) (8) Fuel Blending - Pressure relief valve (V-004) WRR Environmental Services Co., Inc. was previously cited for a violation of this Occupational Safety and Health standard (29 CFR 1910.119(j)(4)(iv)), which was contained in OSHA inspection number 512519, citation number 1 item 6b and was affirmed as final order on January 30, 2013, with respect to their workplace located at 5200 Ryder Road, Eau Claire, WI.