Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 451379.015
Citation: 01059
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,500.00
Current Penalty: $5,500.00
Issuance Date: 11/26/2012
Nr Instances: 1
Nr Exposed: 12
Abatement Date:
Gravity: 5
Report ID: 0522500
Contest Date: 12/12/2012
Final Order: 03/10/2014
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/13/2014 | $5,500.00 | Serious | ||
Penalty | C: Contested | 12/19/2012 | $5,500.00 | Serious | ||
Penalty | Z: Issued | 11/26/2012 | $5,500.00 | Serious |
Text For Citation: 01 Item/Group: 059 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed: a. On the 30th of May 2012, in the control room of the phosphites plant there was a junction box with an unused opening mounted adjacent to the North door. b. On July 27, 2012, in the office building walkway outside of the main lobby mens restroom, there was a subpanel box that was not dead front. The main circuit was open without a breaker or other enclosure and live parts were visible. This was labeled main lower lobby in pen above the cabinet. The main switch or circuit was empty exposing a high voltage conductor.