Violation Detail
Standard Cited: 19100303 B01 II General.
Inspection Nr: 1207843.015
Citation: 01037
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,070.00
Current Penalty: $2,433.00
Issuance Date: 06/26/2017
Nr Instances: 8
Nr Exposed: 18
Abatement Date: 02/02/2018
Gravity: 5
Report ID: 0215800
Contest Date: 07/09/2017
Final Order: 02/02/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/02/2018 | $2,433.00 | 02/02/2018 | Serious | |
Penalty | C: Contested | 07/26/2017 | $5,070.00 | 07/07/2017 | Serious | |
Penalty | Z: Issued | 06/26/2017 | $5,070.00 | 07/07/2017 | Serious |
Text For Citation: 01 Item/Group: 037 Hazard:
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided: a) On or about 1/31/2017, Machine room: On the back side of the wet end the cylinder shower oscillator had a damaged metal condulete. b) On or about 1/31/2017, Machine room: On the back side of the wet end a metal condulete at the end of the #1 roller was damaged. c) On or about 1/31/2017, Machine room: On the back side of the wet end a plastic condulete box was pulled away from the frame of the P12 screen #4. d) On or about 1/31/2017, Machine room: On the drive side of the dryer the #2 drive motor had broken conduit which exposed wires. e) On or about 2/1/201, Machine room: On the drive side of the calender a section of conduit broke away from a condulete which exposed wires. f) On or about 2/1/2017, Machine room: At the rewinder there was conduit that was broken and pulled away form the frame of the rewinder. g) On or about 2/7/2017, Machine room: The control box on the wrapper located in the dry end was damaged and broken open, exposing wiring. h) On or about 2/16/2017, Machine room: A steam jenny had an open condulete and had conduit broken away from its frame. Abatement certification is required for this item.