Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 641138.015
Citation: 01032
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,600.00
Current Penalty: $2,520.00
Issuance Date: 03/14/2013
Nr Instances: 6
Nr Exposed: 100
Abatement Date: 04/30/2013
Gravity: 5
Report ID: 0214500
Contest Date: 04/01/2013
Final Order: 04/03/2014
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/03/2014 | $2,520.00 | 04/30/2013 | Serious | |
Penalty | C: Contested | 04/03/2013 | $3,600.00 | 04/30/2013 | Serious | |
Penalty | Z: Issued | 03/14/2013 | $3,600.00 | 04/30/2013 | Serious |
Text For Citation: 01 Item/Group: 032 Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. a) 421 East 16th Street, Finishing Room: Flexible cord was used as fixed wiring to energize a ceiling mounted fluorescent shop light, on or about 9/24/2012. b) 421 East 16th Street, Finishing Room: Flexible cord was used as fixed wiring to energize a Jensen folder machine, on or about 1/15/2013. c) 421 East 16th Street, Finishing Room: Flexible cord was used as fixed wiring to energize a Kannesegiesser folder machine, on or about 9/24/2012. d) 421 East 16th Street, Finishing Room: Flexible cord was used as fixed wiring to energize a M&M bundle tying machine, on or about 9/24/2012. e) 421 East 16th Street, Milnor Wash System Room: Flexible cord was used as fixed wiring to energize the lint trap motor, on or about 9/24/2012. f) 436 East 16th Street, Front Room: Flexible cord was used as fixed wiring to energize the Chicago automatic folder machine, on or about 10/18/2012.