Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 999111.015
Citation: 01030C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/06/2015
Nr Instances: 4
Nr Exposed: 2
Abatement Date: 04/13/2015
Gravity: 1
Report ID: 0625400
Contest Date:
Final Order: 05/19/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/19/2015 | $0.00 | 04/13/2015 | Serious | |
Penalty | Z: Issued | 04/06/2015 | $0.00 | 04/13/2015 | Serious |
Text For Citation: 01 Item/Group: 030C Hazard:
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: On or about October 08, 2014, and at times prior thereto, the employer did not ensure that junction boxes were covered in the Heat Treat Department, exposing employees to the hazard of electrical shock. a. On mold oven #4, wiring for the 110 Volt junction box was missing covers in two areas. b. On mold oven # 2, the transformers were missing covers on both sides of the oven.