Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1046944.015
Citation: 01025
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,100.00
Current Penalty: $1,200.00
Issuance Date: 09/14/2015
Nr Instances: 3
Nr Exposed: 4
Abatement Date: 10/16/2015
Gravity: 1
Report ID: 0627500
Contest Date:
Final Order: 10/09/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/09/2015 | $1,200.00 | 10/16/2015 | Serious | |
Penalty | Z: Issued | 09/14/2015 | $2,100.00 | 09/18/2015 | Serious |
Text For Citation: 01 Item/Group: 025 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about March 17, 2015, in the EPTD Press Area of Building #1, electrical cables were not provided with strain relief that would prevent pull from being directly transmitted to joints or terminal screws; employees were exposed to electrical shock hazards in the following instances; (a) Next to the OAK LAM Press #30, the strain relief to the 115V WELDOTRON Malfunction Detector Control Box electrical power cable was broken. (b) Next to the Minster Press #60, the strain relief to the 115V WELDOTRON Malfunction Detector Control Box electrical power cable was broken. (c) Next to the Minster Press #60, the strain relief to the BRUDERER 18260-1000 Sheet & Strip Straightener electrical power cable was broken.