Violation Detail
Standard Cited: 19100303 G01 VII B General.
Inspection Nr: 1342920.015
Citation: 01022
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,819.00
Current Penalty: $3,205.00
Issuance Date: 02/25/2019
Nr Instances: 4
Nr Exposed: 7
Abatement Date: 11/13/2020
Gravity: 5
Report ID: 0627500
Contest Date: 03/15/2019
Final Order: 09/27/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 09/27/2020 | $3,205.00 | 11/13/2020 | Serious | |
Penalty | C: Contested | 03/19/2019 | $6,819.00 | 03/07/2019 | Serious | |
Penalty | Z: Issued | 02/25/2019 | $6,819.00 | 03/07/2019 | Serious |
Text For Citation: 01 Item/Group: 022 Hazard:
29 CFR 1910.303(g)(1)(vii)(B): Outdoor electric equipment was not installed in suitable enclosures and/or was not protected from accidental contact by unauthorized personnel, by accidental spillage or leakage from piping systems. On or about August 28, 2018, outside and behind the production floor building, employees were exposed to electrical shock hazards in three instances due to electrical panels and control boxes not being closed or enclosed and protected against accidental spillage or leakage from piping systems; a) Gray electrical box near the outside production area with the door not latched closed. b) Red electrical box near the outside production area with the door not latched closed. c) Control panel for conveyors with lid propped open.