Violation Detail
Standard Cited: 19100305 E02 Wiring methods, components, and equipment for general use.
Inspection Nr: 1109295.015
Citation: 01021
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $600.00
Issuance Date: 02/16/2016
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 03/02/2016
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 03/16/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/16/2016 | $600.00 | 03/02/2016 | Serious | |
Penalty | Z: Issued | 02/16/2016 | $2,800.00 | 03/02/2016 | Serious |
Text For Citation: 01 Item/Group: 021 Hazard:
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures: The employer had a circuit breaker panel and two knife throw switches for dust collection motors along the West wall in the CNC room where water leaked during rainy conditions. The enclosures for the electrical were not weatherproof when exposed to wet/damp locations.