Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1069945.015
Citation: 01021
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $3,500.00
Issuance Date: 12/09/2015
Nr Instances: 1
Nr Exposed: 50
Abatement Date: 01/13/2016
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 01/06/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/06/2016 | $3,500.00 | 01/13/2016 | Serious | |
Penalty | Z: Issued | 12/09/2015 | $5,000.00 | 01/13/2016 | Serious |
Text For Citation: 01 Item/Group: 021 Hazard:
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. a. At the workplace, in the powder coating area, electrical equipment including, but not limited to, three duplex receptacle outlets, an electric drinking water cooler and a relocatable power tap in a Class II, Division 2 location were not intrinsically safe, approved for a Class II, Division 2 location, or safe for a Class II, Division 2 location.