Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 757902.015
Citation: 01020B
Citation Type: Serious
Abatement Date: 03/27/2015 2
Initial Penalty: $5,390.00
Current Penalty: $0.00
Issuance Date: 05/08/2013
Nr Instances: 2
Nr Exposed: 15
Related Event Code (REC):
Gravity: 10
Report ID: 0213100
Contest Date: 05/31/2013
Final Order: 02/27/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/27/2015 | $0.00 | 03/27/2015 | Serious | |
Penalty | C: Contested | 06/03/2013 | $5,390.00 | 05/30/2013 | Serious | |
Penalty | Z: Issued | 05/08/2013 | $5,390.00 | 05/30/2013 | Serious |
Text For Citation: 01 Item/Group: 020B Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) Shavings Room - On or around December 30, 2012, Class II Explosive Wood Dust was suspended in air during times including but not limited to, normal operations and a blow down cleaning procedure. An accumulation of dust was observed on electrical equipment. General purpose wiring, breaker panel boxes, disconnect switches, receptacles, lighting, and electric motors were not dust tight ignition proof and approved for Class II Division 1 locations. b) Bagger Room - On or around December 30, 2012, Class II Explosive Wood Dust was suspended in air during times including but not limited to, normal operations and a blow down cleaning procedure. An accumulation of dust was observed on electrical equipment, controls, motors, and panel boxes. General purpose wiring, breaker panel boxes, disconnect switches, receptacles, lighting, and electric motors were not dust tight ignition proof and approved for Class II Division 1 locations.