Violation Detail
Standard Cited: 19100119 J02 Process safety management of highly hazardous chemicals.
Inspection Nr: 311917009
Citation: 01020
Citation Type: Serious
Abatement Status: X
Initial Penalty: $5,000.00
Current Penalty: $5,000.00
Issuance Date: 05/13/2009
Nr Instances: 2
Nr Exposed: 24
Abatement Date: 06/29/2010
Gravity: 10
Report ID: 0213400
Contest Date: 06/03/2009
Final Order: 12/24/2009
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | R: Review Commission | 12/24/2009 | $5,000.00 | 06/29/2010 | Serious | |
| Penalty | J: ALJ Decision | 08/28/2009 | $5,000.00 | 06/29/2010 | Serious | |
| Penalty | Z: Issued | 05/13/2009 | $5,000.00 | 06/29/2009 | Serious |
Text For Citation: 01 Item/Group: 020 Hazard: REFINERY
29 CFR 1910.119(j)(2): The employer did not implement written procedures to maintain the on-going integrity of process equipment: a- Hess Port Reading Refinery - The employer failed to implement written procedures to maintain safety critical instruments to include but not limited to flow, temperature and pressure indicators/alarms/control valves. Such equipment can be found on pressure vessels to include but not limited to T-501R Main Column, D-507R Main Column Overhead Receiver, T-601R Primary Absorber and D-601R Compressor Suction Drum. Condition noted on or about 03/09/09. b- Hess Port Reading Refinery - The employer failed to implement their CUI program with pipe systems identified as susceptible to CUI to include but not limited to piping throughout FCCU, Gas Con and Alky observed with damaged and/or missing insulation. Conditions noted on or about 02/27/09.s