Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1069945.015
Citation: 01020
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $3,500.00
Issuance Date: 12/09/2015
Nr Instances: 2
Nr Exposed: 10
Abatement Date: 12/21/2015
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 01/06/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/06/2016 | $3,500.00 | 12/21/2015 | Serious | |
Penalty | Z: Issued | 12/09/2015 | $5,000.00 | 12/21/2015 | Serious |
Text For Citation: 01 Item/Group: 020 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a. At the workplace, in the wire room, on the North side, there was an unused opening on the bottom of the 480 VAC electrical disconnect for the pointer, thereby exposing employees to an electrical hazard. b. At the workplace, in the wire room, on the West wall, there was an unused opening on the bottom of the 480 VAC electrical disconnect for the lifting magnet, thereby exposing employees to an electrical hazard.