Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 1011711.015
Citation: 01020
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $1,600.00
Current Penalty: $1,060.00
Issuance Date: 05/27/2015
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 06/27/2015
Gravity: 5
Report ID: 0213600
Contest Date: 06/19/2015
Final Order: 03/18/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 03/18/2016 | $1,060.00 | 06/27/2015 | Serious | |
Penalty | C: Contested | 06/24/2015 | $1,600.00 | 06/27/2015 | Serious | |
Penalty | Z: Issued | 05/27/2015 | $1,600.00 | 06/27/2015 | Serious |
Text For Citation: 01 Item/Group: 020 Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: a) On or about 12/4/14 in the phosgene cylinder room; employer failed to protect employees against contact with energized electrical conductors ( 240 volts AC ) when the lower circuit breaker slots, inside the dead front electrical panel at the south end near the exit door, were missing covers. b) On or about 12/4/14 in the phosgene cylinder room; employer failed to protect employees against a fire hazard when the disconnect for Pump #2, 240 volts AC, was missing knockouts. ABATEMENT CERTIFICATION REQUIRED