Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 1006716.015
Citation: 01020
Citation Type: Serious
Abatement Date: 05/19/2015 2
Initial Penalty: $4,900.00
Current Penalty: $2,695.00
Issuance Date: 04/29/2015
Nr Instances: 3
Nr Exposed: 15
Related Event Code (REC):
Gravity: 10
Report ID: 0522500
Contest Date:
Final Order: 05/22/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/22/2015 | $2,695.00 | 05/19/2015 | Serious | |
Penalty | Z: Issued | 04/29/2015 | $4,900.00 | 05/19/2015 | Serious |
Text For Citation: 01 Item/Group: 020 Hazard:
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. a. In the electrical room, the black 4 gauge wire used to energize the Leeson Model C6T17FC9H Motor in the Head House, was not grounded. Employees were exposed to an electrical contact hazard. b. In the "old set up", the flexible cord was missing the ground pin. Employees were exposed to an electrical contact hazard. c. In the bagging area, the flexible cord for the fan was missing the grounding pin. Employees were exposed to an electrical contact hazard.