Violation Detail
Standard Cited: 19100305 A02 V C Wiring methods, components, and equipment for general use.
Inspection Nr: 1366023.015
Citation: 01019A
Citation Type: Serious
Abatement Date: 04/09/2019 2
Initial Penalty: $8,525.00
Current Penalty: $4,000.00
Issuance Date: 04/03/2019
Nr Instances: 1
Nr Exposed: 100
Related Event Code (REC):
Gravity: 5
Report ID: 0111700
Contest Date: 04/23/2019
Final Order: 04/27/2022
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/27/2022 | $4,000.00 | 04/09/2019 | Serious | |
Penalty | C: Contested | 04/26/2019 | $8,525.00 | 04/09/2019 | Serious | |
Penalty | Z: Issued | 04/03/2019 | $8,525.00 | 04/09/2019 | Serious |
Text For Citation: 01 Item/Group: 019A Hazard:
29 CFR 1910.305(a)(2)(v)(C): Branch-circuit conductors were laid on the floor. Shipping Area exterior building exit- Employees entering and exiting the facility were not protected from an electric shock hazard where a 480 volt branch circuit was placed directing on the ground outside the exit to provide power to a temporary air compressor. The 480 volt branch circuit was placed on the ground between the building and compressor where employees walk from the parking lot and step on the branch circuit; which was evident due to the foot prints in the snow.