Violation Detail
Standard Cited: 19100305 G01 IV Wiring methods, components, and equipment for general use.
Inspection Nr: 1107787.015
Citation: 01018A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $1,600.00
Current Penalty: $940.00
Issuance Date: 05/13/2016
Nr Instances: 3
Nr Exposed: 11
Abatement Date: 06/09/2016
Gravity: 5
Report ID: 0336000
Contest Date:
Final Order: 06/07/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/07/2016 | $940.00 | 06/09/2016 | Serious | |
Penalty | Z: Issued | 05/13/2016 | $1,600.00 | 06/09/2016 | Serious |
Text For Citation: 01 Item/Group: 018A Hazard:
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv): A.) Instance A deleted during Informal Conference B.) Falls Creek Powdered Metals, Inc., 82 Industrial Drive, Brockway, PA 15824, air compressor room, on or about November 23, 2015 and times prior thereto: A flexible electrical extension cord was used to power a fan in the air compressor room. The flexible electrical extension cord was used as a substitute for the fixed wiring of a structure. C.) Falls Creek Powdered Metals, Inc., 82 Industrial Drive, Brockway, PA 15824, production area, on or about November 23, 2015 and times prior thereto: A flexible cord for a lighting fixture on press M4 was plugged in to a receptacle on the opposite side of the wall, and ran through a wall opening to the press. The flexible cord was routed along building surfaces, through wall opening, exposed to damage/chaffing from the sharp metal edge of the metal wall construction.