Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 985617.015
Citation: 01017A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $3,000.00
Issuance Date: 01/09/2015
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 01/26/2015
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 02/03/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/03/2015 | $3,000.00 | 01/26/2015 | Serious | |
Penalty | Z: Issued | 01/09/2015 | $5,000.00 | 01/26/2015 | Serious |
Text For Citation: 01 Item/Group: 017A Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) The Allen Bradley disconnect labeled 480 volt three phase mounted to the wall in the de barker addition had two knockout plugs missing in the bottom of the disconnect at the time of the inspection on 7/17/2014. b) The large junction box in the chipper electrical room was not securely closed allowing saw dust to enter the cabinet.