Violation Detail
Standard Cited: 19100303 G01 General.
Inspection Nr: 1229034.015
Citation: 01017
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,967.00
Current Penalty: $4,125.00
Issuance Date: 10/31/2017
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 09/25/2018
Gravity: 5
Report ID: 0418100
Contest Date: 11/23/2017
Final Order: 09/04/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 09/04/2018 | $4,125.00 | 09/25/2018 | Serious | |
Penalty | C: Contested | 12/13/2017 | $7,967.00 | 11/28/2017 | Serious | |
Penalty | Z: Issued | 10/31/2017 | $7,967.00 | 11/28/2017 | Serious |
Text For Citation: 01 Item/Group: 017 Hazard:
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On 5/2/17, at the Buford facility in Building 1 at the Hidro/Fritz #2 electrical panel, the working space for the equipment was 9 inches and the doors to the cabinet could not be opened all the way due to powered industrial truck guardrails blocking the doors.