Violation Detail
Standard Cited: 19100119 J06 II Process safety management of highly hazardous chemicals.
Inspection Nr: 311907711
Citation: 01016
Citation Type: Serious
Abatement Date: 12/12/2009 X
Initial Penalty: $2,250.00
Current Penalty: $4,800.00
Issuance Date: 03/05/2009
Nr Instances: 1
Nr Exposed: 13
Related Event Code (REC):
Gravity: 03
Report ID: 0830500
Contest Date: 03/24/2009
Final Order: 11/12/2009
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/12/2009 | $4,800.00 | 12/12/2009 | Serious | |
Penalty | Z: Issued | 03/05/2009 | $2,250.00 | 04/07/2009 | Serious |
Text For Citation: 01 Item/Group: 016 Hazard: ELECTRIC
29 CFR 1910.119(j)(6)(ii): Appropriate checks and inspections were not performed to assure that equipment was installed properly and consistent with design specifications and manufacturer's instructions: (a)Suncor Energy (U.S.A.), Inc., 5801 Brighton Blvd., Commerce City, Colorado: On or about December 17, 2008, and at times prior thereto, the employer did not perform an appropriate test and inspection of the gas (hydrogen sulfide and flammable vapors) detection and HVAC system for the Asphalt Unit Control Room building to assure it was installed to operate in accordance with its design and the manufacturer's instructions. Employees were exposed to hazards associated with potential overexposures to hydrogen sulfide and potentially explosive concentrations of flammable vapors in a non-classified electrical location. One feasible means of abatement would be for the employer to institute a management system which ensures that appropriate tests and inspections of newly installed equipment are performed to ensure such equipment operates in accordance with its design specifications and the manufacturer's instructions. Abatement Note: Abatement certification and documentation are required for this item (see enclosed "Sample Abatement-Certification Letter").