Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1367898.015
Citation: 01016
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,630.00
Current Penalty: $4,215.00
Issuance Date: 06/18/2019
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 07/10/2019
Gravity: 5
Report ID: 0521400
Contest Date:
Final Order: 07/09/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/09/2019 | $4,215.00 | 07/10/2019 | Serious | |
Penalty | Z: Issued | 06/18/2019 | $6,630.00 | 07/10/2019 | Serious |
Text For Citation: 01 Item/Group: 016 Hazard:
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: On or about December 27, 2018, the circuit breakers protecting the circuits for the salt to salt line 2 were not labeled. This condition exposed employees to electric shock and burn hazards from accidental actuation or inability to turn off the power. Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).