Violation Detail
Standard Cited: 19100107 D03 Spray finishing using flammable and combustible materials.
Inspection Nr: 1078995.015
Citation: 01016
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $2,000.00
Issuance Date: 11/30/2015
Nr Instances: 10
Nr Exposed: 20
Abatement Date: 04/20/2017
Gravity: 5
Report ID: 0524500
Contest Date: 12/15/2015
Final Order: 03/20/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/20/2017 | $2,000.00 | 04/20/2017 | Serious | |
Penalty | C: Contested | 12/22/2015 | $0.00 | 01/19/2016 | Serious | |
Penalty | Z: Issued | 11/30/2015 | $0.00 | 01/19/2016 | Serious |
Text For Citation: 01 Item/Group: 016 Hazard:
29 CFR 1910.107(d)(3): Each spray booth with more than one fan serving one booth, did not have the fans interconnected so that one fan cannot operate without all fans being operated. Employees in Paint Booths #1 and #2 were exposed to burn and smoke inhalation hazards and the employer did not interconnect the exhaust fans to ensure one fan could not operate without all fans being operational.