Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1077467.015
Citation: 01016
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,930.00
Current Penalty: $6,930.00
Issuance Date: 12/24/2015
Nr Instances: 1
Nr Exposed: 20
Abatement Date: 02/12/2016
Gravity: 10
Report ID: 0729300
Contest Date:
Final Order: 01/21/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/21/2016 | $6,930.00 | 02/12/2016 | Serious | |
| Penalty | Z: Issued | 12/24/2015 | $6,930.00 | 02/12/2016 | Serious |
Text For Citation: 01 Item/Group: 016 Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed: a/ At the Kieserling Line, a flexible cord entering a motor unit was subjected to abrasion due to the vibration caused by moving machine parts throughout the line. The opening through which this flexible cord entered was not effectively closed.