Violation Detail
Standard Cited: 19100037 A04 Maintenance, safeguards, and operational features for exit routes.
Inspection Nr: 1207843.015
Citation: 01015A
Citation Type: Serious
Abatement Date: 04/03/2018 2
Initial Penalty: $6,338.00
Current Penalty: $3,042.00
Issuance Date: 06/26/2017
Nr Instances: 7
Nr Exposed: 24
Related Event Code (REC):
Gravity: 5
Report ID: 0215800
Contest Date: 07/09/2017
Final Order: 02/02/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 02/02/2018 | $3,042.00 | 04/03/2018 | Serious | |
Penalty | C: Contested | 07/26/2017 | $6,338.00 | 07/07/2017 | Serious | |
Penalty | Z: Issued | 06/26/2017 | $6,338.00 | 07/07/2017 | Serious |
Text For Citation: 01 Item/Group: 015A Hazard:
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: a) On or about 1/31/2017, Machine room: A fire alarm horn, located on the drive side wall, was disabled. b) On or about 2/1/2017, Locker room: An existing emergency light was not operational. c) On or about 2/7/2017, Machine room: Sprinkler heads located on the dry end of the machine room were not maintained, in that they were caked with paper dust. d) On or about 2/7/2017, Basement: An existing emergency light near the stairs to the compressor room was not operational. e) On or about 2/7/2017, Basement: An existing emergency light near the MCC#2 was not operational. f) On or about 2/15/2017, Pulper Room: An existing emergency light was not functional. g) On or about 2/16/2017, Warehouse: An existing exit sign in the South West corner of the building was not operational as it was not lit as designed. Abatement certification is required for these items.