Violation Detail
Standard Cited: 19100303 G01 I B General.
This violation item has been deleted.
Inspection Nr: 1077467.015
Citation: 01015A
Citation Type: Serious
Abatement Status:
Initial Penalty: $6,930.00
Current Penalty: $0.00
Issuance Date: 12/24/2015
Nr Instances: 2
Nr Exposed: 1
Abatement Date: 02/12/2016
Gravity: 10
Report ID: 0729300
Contest Date:
Final Order: 01/21/2016
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/21/2016 | $0.00 | 02/12/2016 | Serious | |
Penalty | Z: Issued | 12/24/2015 | $6,930.00 | 02/12/2016 | Serious |
Text For Citation: 01 Item/Group: 015A Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : a/ Inside of Building #2, specifically along the rear aisleway of the Draw Bench Line, objects including, but not limited to, a wooden bench and 55-gallon drums were located in the designated aisleway which ran parallel to the 480 volt distribution panel boxes. These objects were generally 20 inches away from the panel boxes.