Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1146111.015
Citation: 01015
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,236.00
Current Penalty: $4,286.00
Issuance Date: 10/27/2016
Nr Instances: 2
Nr Exposed: 20
Abatement Date: 07/07/2017
Gravity: 5
Report ID: 0215800
Contest Date: 11/10/2016
Final Order: 08/17/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 08/17/2017 | $4,286.00 | 07/07/2017 | Serious | |
Penalty | C: Contested | 11/30/2016 | $6,236.00 | 11/08/2016 | Serious | |
Penalty | Z: Issued | 10/27/2016 | $6,236.00 | 11/08/2016 | Serious |
Text For Citation: 01 Item/Group: 015 Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) On or about 5/6/2016, Mixing Area: Employees are exposed to energized electrical parts while inside of a mixer control box. b) On or about 6/7/2016, South Side Shop Area: Employees are exposed to energized electrical parts inside of an electrical box mounted next to the break room door. Abatement certification is required for these items.