Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 997958.015
Citation: 01014B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/17/2015
Nr Instances: 2
Nr Exposed: 1
Abatement Date: 07/06/2016
Gravity:
Report ID: 0112000
Contest Date: 03/10/2015
Final Order: 06/06/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/06/2016 | $0.00 | 07/06/2016 | Other | |
Penalty | C: Contested | 03/12/2015 | $0.00 | 04/03/2015 | Serious | |
Penalty | Z: Issued | 02/17/2015 | $0.00 | 04/03/2015 | Serious |
Text For Citation: 01 Item/Group: 014B Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater: A. Crane Pulpit: On, or about, October 8, 2014, a storage cabinet was located next to a Square D circuit breaker panel, reducing the width of the working space to 28 inches B. Water Treatment Building/Demin: Transformer PTR-1B4 was located partially in the working space for panelboard PP-1B4, reducing the width of the working space to 25.5 inches.