Violation Detail
Standard Cited: 19100305 A02 X Wiring methods, components, and equipment for general use.
Inspection Nr: 1558914.015
Citation: 01014A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,502.00
Current Penalty: $10,000.00
Issuance Date: 04/14/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 05/03/2022
Gravity: 10
Report ID: 0627500
Contest Date:
Final Order: 05/04/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/04/2022 | $10,000.00 | 05/03/2022 | Serious | |
Penalty | Z: Issued | 04/14/2022 | $14,502.00 | 05/03/2022 | Serious |
Text For Citation: 01 Item/Group: 014A Hazard:
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points. Cold Sheer Electrical Control Room: On or about October 28, 2021, the employer did not ensure a 480v flat cable was protected from a pinch point. The cable was run through the bottom of the heavy metal entrance door. This condition exposed employees to death or 2nd and 3rd degree burns from electrical shock.