Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 980337.015
Citation: 01014
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $1,820.00
Issuance Date: 11/28/2014
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 03/31/2015
Gravity: 10
Report ID: 0418100
Contest Date:
Final Order: 01/30/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/30/2015 | $1,820.00 | 03/31/2015 | Serious | |
Penalty | Z: Issued | 11/28/2014 | $2,800.00 | 12/24/2014 | Serious |
Text For Citation: 01 Item/Group: 014 Hazard:
29 CFR 1910.307(c): Electrical equipment in a hazardous (classified) location was not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: On or about June 10, 2014 at 120 McArthur Road, Marble Hill, GA: Electrical equipment including but not limited to lights used in the spray area, a Class II, Division I location were not intrinsically safe, approved for a Class II, Division I location, or safe for a Class II, Division I location.