Violation Detail
Standard Cited: 19100305 E02 Wiring methods, components, and equipment for general use.
Inspection Nr: 1643528.015
Citation: 01014
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $6,250.00
Current Penalty: $0.00
Issuance Date: 05/31/2023
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 07/19/2023
Gravity: 10
Report ID: 0418100
Contest Date: 06/26/2023
Final Order: 08/14/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/14/2024 | $0.00 | 07/19/2023 | Serious | |
Penalty | C: Contested | 06/30/2023 | $6,250.00 | 07/19/2023 | Serious | |
Penalty | Z: Issued | 05/31/2023 | $6,250.00 | 07/19/2023 | Serious |
Text For Citation: 01 Item/Group: 014 Hazard:
29 CFR 1910.305(e)(2): Switches, circuit breakers and switchboards installed in wet locations were not enclosed in weatherproof enclosures: a) Block Saw Room; on or about January 11, 2023 and at times prior to, employees were exposed to electrical shock and burn hazards, in that the employer did not ensure that the starters for the sump pumps were mounted inside waterproof enclosures to prevent damage from water and slurry, and accidental contact with 240 V and 480 V sources.