Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1567218.015
Citation: 01014
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,357.00
Current Penalty: $11,350.20
Issuance Date: 06/03/2022
Nr Instances: 3
Nr Exposed: 3
Abatement Date: 07/15/2022
Gravity: 10
Report ID: 0418200
Contest Date:
Final Order: 06/28/2022
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/28/2022 | $11,350.20 | 07/15/2022 | Serious | |
Penalty | Z: Issued | 06/03/2022 | $14,357.00 | 06/30/2022 | Serious |
Text For Citation: 01 Item/Group: 014 Hazard:
29 CFR 1910.303(g)(2)(i):Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Dock Pit: On December 6, 2021, and at times prior, the employer exposed employees to electrical hazards of 480 volts, in that; the enclosure of the control panel for the water pump was damaged such that the interior, including conductors, were exposed as employees operated it. b) Fabrication Shop: On December 6, 2021, and at times prior, the employer exposed employees to electrical hazards of 480 volts, in that; the front enclosures of the live electrical panels in the fabrication shop were removed or missing, leaving conductors unprotected. c) Processing Area: On December 6, 2021, and at times prior, the employer exposed employees to electrical hazards of 480 volts, in that; the front enclosures of the live electrical panels behind the dewatering machine were removed or missing, leaving conductors unprotected.