Violation Detail
Standard Cited: 19100305 J04 VI Wiring methods, components, and equipment for general use.
Inspection Nr: 1196279.015
Citation: 01014
Citation Type: Serious
Abatement Date: 02/09/2017 2
Initial Penalty: $3,802.00
Current Penalty: $2,281.20
Issuance Date: 02/03/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 1
Report ID: 0420600
Contest Date:
Final Order: 03/05/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/05/2017 | $2,281.20 | 02/09/2017 | Serious | |
Penalty | Z: Issued | 02/03/2017 | $3,802.00 | 02/09/2017 | Serious |
Text For Citation: 01 Item/Group: 014 Hazard:
29 CFR 1910.305(j)(4)(vi): Individual disconnecting means were not provided for each motor: a. High Bay area, employees were exposed to a struck by hazard, in that, the two Bridgestone Milling machines were hard wired and were not provided with a main disconnect so that the machines could be isolated from their power supply, on or about 12/08/2016.