Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1023693.015
Citation: 01014
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,300.00
Current Penalty: $4,410.00
Issuance Date: 07/30/2015
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 08/11/2015
Gravity: 10
Report ID: 0523400
Contest Date: 08/20/2015
Final Order: 01/22/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/22/2016 | $4,410.00 | 08/11/2015 | Serious | |
Penalty | C: Contested | 08/25/2015 | $6,300.00 | 08/11/2015 | Serious | |
Penalty | Z: Issued | 07/30/2015 | $6,300.00 | 08/11/2015 | Serious |
Text For Citation: 01 Item/Group: 014 Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: (a) Wastewater Treatment: Flexible electrical cable for a 208 volt pendant box outlet was wired into electrical Panel Box 22 by running the cable under the dead front panel and between the electrical box frame subjecting the cable to abrasion and pinching damage. This exposed employees to an electrical shock hazard.