Violation Detail
Standard Cited: 19100335 A01 II Safeguards for personnel protection.
Inspection Nr: 1194248.015
Citation: 01013C
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/27/2017
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 03/29/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/29/2017 | $0.00 | Serious | ||
Penalty | Z: Issued | 02/27/2017 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 013C Hazard:
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested: Company: On, or about, November 30, 2016, a pair of Salisbury Class 0 voltage rated gloves that were currently in service has last been inspected in September, 2012, Per Table I-6 included in 29 CFR 1910.137, insulated equipment may not be placed into service more than 12 months after it has been electrically tested.