Violation Detail
Standard Cited: 19100303 G01 I C General.
Inspection Nr: 1619294.015
Citation: 01013B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/10/2023
Nr Instances: 2
Nr Exposed: 4
Abatement Date: 02/28/2023
Gravity: 1
Report ID: 0112000
Contest Date: 02/06/2023
Final Order: 04/05/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/05/2023 | $0.00 | 02/28/2023 | Other | |
Penalty | C: Contested | 02/06/2023 | $0.00 | 02/28/2023 | Serious | |
Penalty | Z: Issued | 01/10/2023 | $0.00 | 02/28/2023 | Serious |
Text For Citation: 01 Item/Group: 013B Hazard:
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of work space was not clear and did not extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of 29 CFR 1910.303. Other equipment associated with the installation and located above or below the electric equipment extended more than 153 mm (6 In.( beyond the front of the electric equipment: A. South Building, Near Loading Dock: On, or about, November 1, 2022, an ACME transformer was installed in the working space for panel 2FLRSLV1, a Square D Load Center. B. South Building, Rewind Area at Press #2: On, or about, November 1, 2022, a Challenger transformer was installed in the working space for panel SB1FWALV1, a Square D panel board and a Square D disconnect switch.