Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1721955.015
Citation: 01013A
Citation Type: Serious
Abatement Date: 08/12/2024 2
Initial Penalty: $16,131.00
Current Penalty: $16,131.00
Issuance Date: 07/18/2024
Nr Instances: 1
Nr Exposed: 7
Related Event Code (REC):
Gravity: 10
Report ID: 0419400
Contest Date: 08/06/2024
Final Order: 11/27/2024
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 11/27/2024 | $16,131.00 | 08/12/2024 | Serious | |
Penalty | C: Contested | 10/10/2024 | $16,131.00 | 08/12/2024 | Serious | |
Penalty | Z: Issued | 07/18/2024 | $16,131.00 | 08/12/2024 | Serious |
Text For Citation: 01 Item/Group: 013A Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) Powder room - On or about January 25, 2024, the employer did not ensure that the electrical equipment, such as lighting, electrical raceways, and conduit in a Class II Division 1 location was approved for a Class II, Division 1 location containing explosive 3M Scotchkote Fusion-Bonded Epoxy Coating dust accumulations exposing employees to explosion and fire hazards.