Violation Detail
Standard Cited: 19100119 M05 Process safety management of highly hazardous chemicals.
Inspection Nr: 312487457
Citation: 01013
Citation Type: Serious
Abatement Status: W
Initial Penalty: $5,000.00
Current Penalty: $7,000.00
Issuance Date: 07/08/2009
Nr Instances: 2
Nr Exposed: 12
Abatement Date: 08/10/2009
Gravity: 10
Report ID: 0317000
Contest Date: 07/28/2009
Final Order: 01/17/2012
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/17/2012 | $7,000.00 | 08/10/2009 | Serious | |
Penalty | Z: Issued | 07/08/2009 | $5,000.00 | 08/10/2009 | Serious |
Text For Citation: 01 Item/Group: 013 Hazard: REFINERY
29 CFR 1910.119(m)(5): The employer did not establish a system to promptly and effectively address and resolve the incident report findings and recommendations: a) Sunoco, Inc. Marcus Hook Refinery,10-4 FCCU - The employer did not promptly and effectively address the incident investigation findings and recommendations regarding the inability of the Operators to access and operate the wet gas discharge valve located at the exchangers. Condition noted on or about January 29, 2009. b) Sunoco, Inc. Marcus Hook Refinery, 10-4 FCCU - The employer did not promptly and effectively address the incident investigation findings and recommendations regarding the inability of the Operators to access and operate the wet gas compressor by-pass valve. Condition noted on or about March 10, 2009. NOTE: DOCUMENTATION OF ABATEMENT OF THIS CONDITION IS REQUIRED