Violation Detail
Standard Cited: 19100303 B02 General.
This violation item has been deleted.
Inspection Nr: 1366023.015
Citation: 01013
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,525.00
Current Penalty: $0.00
Issuance Date: 04/03/2019
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 04/22/2019
Gravity: 5
Report ID: 0111700
Contest Date: 04/23/2019
Final Order: 04/27/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/27/2022 | $0.00 | 04/22/2019 | Serious | |
Penalty | C: Contested | 04/26/2019 | $8,525.00 | 04/22/2019 | Serious | |
Penalty | Z: Issued | 04/03/2019 | $8,525.00 | 04/22/2019 | Serious |
Text For Citation: 01 Item/Group: 013 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a. Milling- Employees working from the ground around the double edge bander were not protected from struck by and arc flash hazards where the Square D plug in tap box for the double edge bander was not supported as required by the listing and labeling requirements. The employer was using a ratchet strap to support and secure the tap box in place on the Square D busway. b. Milling and Shipping- The 480 volt service disconnect #2 milling panel board and two 480 volt panel boards located in the mill near the Koch bore and dowel machine and the shipping area were not installed as required where sheet metal was used to cover openings over missing circuit breakers instead of listed and labeled Square D filler plates.