Violation Detail
Standard Cited: 19100304 C04 Wiring design and protection.
Inspection Nr: 1299619.015
Citation: 01013
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,696.00
Current Penalty: $3,696.00
Issuance Date: 08/24/2018
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 09/18/2018
Gravity: 5
Report ID: 0626000
Contest Date:
Final Order: 09/19/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 08/24/2018 | $3,696.00 | 09/18/2018 | Serious |
Text For Citation: 01 Item/Group: 013 Hazard:
29 CFR 1910.304(c)(4): Outside conductors rated 600 volts, nominal, or less did not have a clearance of at least 8 feet from the highest point of roofs over which they pass: On February 28, 2018, and times prior thereto, at this establishment, adjacent to the storage shop and sidewalk; An energized outside conductor had a clearance less than 8 feet from the highest point of the roof.