Violation Detail
Standard Cited: 19100305 G01 IV B Wiring methods, components, and equipment for general use.
Inspection Nr: 1375672.015
Citation: 01012C
Citation Type: Serious
Abatement Date: 1
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/07/2019
Nr Instances: 2
Nr Exposed: 10
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 07/09/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/09/2019 | $0.00 | Serious | ||
Penalty | Z: Issued | 06/07/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 012C Hazard:
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: A. Building 3, Main Aisle near QC Office: On, or about, March 14, 2019, a flexible cord was run out of the bottom of Panelboard 3I, through a hole in a vertical column, through a hole in a masonry block wall and into an Allen-Bradley wall mounted transformer. B. Building 4, Gold Room Chemical Storage: On, or about, May 14, 2019, a flexible cord was run through a wall opening to energize the thermostat control for the overhead heater.