Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 854183.015
Citation: 01012
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $3,400.00
Current Penalty: $2,040.00
Issuance Date: 02/14/2013
Nr Instances: 2
Nr Exposed: 3
Abatement Date:
Gravity: 5
Report ID: 0728500
Contest Date:
Final Order: 02/28/2013
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/28/2013 | $2,040.00 | Serious | ||
Penalty | Z: Issued | 02/14/2013 | $3,400.00 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) Maintenance Area: There was not adequate strain relief to the Thermal Dynamics welder. At the plug-in there was not adequate strain relief as the outer insulation had pulled back exposing interior wiring where the plug-in joined the cord. (b) Maintenance Area: There was not adequate strain relief for the Thermal Dynamics welder at the rear of the welder where the power cord attached to the welder as the outer insulation had pulled back exposing interior wiring.