Violation Detail
Standard Cited: 19100119 I02 I Process safety management of highly hazardous chemicals.
Inspection Nr: 314505298
Citation: 01012
Citation Type: Serious
Abatement Status: X
Initial Penalty: $2,000.00
Current Penalty: $2,000.00
Issuance Date: 11/09/2010
Nr Instances: 3
Nr Exposed: 23
Abatement Date: 12/03/2010
Gravity: 10
Report ID: 0729300
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
Text For Citation: 01 Item/Group: 012 Hazard: CHEMNEP
29 CFR 1910.119(i)(2)(i): The pre-startup safety review did not confirm that prior to the introduction of highly hazardous chemicals to the process, that construction and equipment were in accordance with design specifications: a.The pre-startup safety review did not identify the lack of exhaust ventilation at the base chemical filling. b. The pre-startup safety review did not identify the lack of exhaust ventilation at the hot water bath tank. c.The Pre-startup safety review did not identify that drainage system was not installed in the floor where flammable chemicals were likely to spill. Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citation(s).n
Translate