Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 D03 III Process safety management of highly hazardous chemicals.

Inspection Nr: 312380512

Citation: 01012

Citation Type: Serious

Abatement Status:

Initial Penalty: $6,300.00

Current Penalty: $6,300.00

Issuance Date: 08/04/2009

Nr Instances: 1

Nr Exposed: 50

Abatement Date: 08/17/2009

Gravity: 10

Report ID: 0627700

Contest Date: 08/24/2009

Final Order:

Related Event Code (REC):

Emphasis:



Text For Citation: 01 Item/Group: 012 Hazard: REFINERY

29 CFR 1910.119(d)(3)(iii): For existing equipment designed and constructed in accordance with codes, standards, or practices that are no longer in general use, the employer does not determine and document that equipment is designed, maintained, inspected, tested and operating in a safe manner: The employer does not have written process safety information for design, maintenance, inspection, testing and operations that determines and documents the safe use and operation of the Crude Unit control room. The control room conditions do not prevent infiltration of hydrocarbons or toxics, do not prevent struck-by hazards, do not prevent fire spread, and do not provide a safe location from blast overpressure conditions. The conditions were observed on or about February 4, 2009, and at times prior to and thereafter, at the Sinclair Tulsa Refinery. Pursuant to 29 CFR 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation describing the actions it is taking to ensure that the Crude Unit control room is designed, maintained, inspected, tested and operating in a safe manner.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close