Violation Detail
Standard Cited: 19100304 F01 IV Wiring design and protection.
Inspection Nr: 1681286.015
Citation: 01012
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $6,250.00
Current Penalty: $3,522.31
Issuance Date: 12/13/2023
Nr Instances: 2
Nr Exposed: 8
Abatement Date:
Gravity: 5
Report ID: 0214500
Contest Date: 01/31/2024
Final Order: 12/20/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 12/20/2024 | $3,522.31 | Serious | ||
Penalty | C: Contested | 02/01/2024 | $6,250.00 | Serious | ||
Penalty | Z: Issued | 12/13/2023 | $6,250.00 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard:
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: a) 1 Raritan Rd., Oakland NJ - Carpentry Shop - Electric Panel between shelves: The electric breakers that controlled the lights as well as motors were blocked by a plywood box and a cart, on or about 7/5/23. b) 1 Raritan Rd., Oakland NJ - Carpentry Shop - Electric Panel at corner: The electric breakers that controlled the lights as well as motors were blocked by tables and other materials, on or about 7/5/23.