Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1191936.015
Citation: 01012
Citation Type: Serious
Abatement Date: 03/21/2017 4
Initial Penalty: $2,390.00
Current Penalty: $2,390.00
Issuance Date: 02/21/2017
Nr Instances: 2
Nr Exposed: 2
Related Event Code (REC): C
Gravity: 1
Report ID: 0111400
Contest Date:
Final Order: 03/20/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 02/21/2017 | $2,390.00 | 03/21/2017 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment is not used or installed in accordance with instructions included in the listing or labeling:(a) Location: Pallet Repair Tables 5 and 6 The violation was observed on November 28th, 2016, when employees were exposed to electric shocks while using receptacles that were designed to be mounted and were lying loosely on the bottom shelf of their pallet repair table: 1) Receptacle box lying on bottom shelf of pallet repair table 5; 2) Receptacle box lying on bottom shelf of pallet repair table 6. To abate this violation, the employer must ensure that receptacles are designed and installed in accordance with instructions included in the listing and labeling. Pursuant to 29 CFR 1903.19, the employer must submit documents describing the steps it is taking to ensure compliance.