Violation Detail
Standard Cited: 19100303 G02 I General.
This violation item has been deleted.
Inspection Nr: 1179460.015
Citation: 01012
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $12,675.00
Current Penalty: $0.00
Issuance Date: 03/14/2017
Nr Instances: 2
Nr Exposed: 20
Abatement Date: 04/03/2017
Gravity: 10
Report ID: 0522500
Contest Date: 04/03/2017
Final Order: 03/19/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/19/2018 | $0.00 | 04/03/2017 | Serious | |
Penalty | C: Contested | 04/10/2017 | $12,675.00 | 04/03/2017 | Serious | |
Penalty | Z: Issued | 03/14/2017 | $12,675.00 | 04/03/2017 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means: a. In the southwest corner of the building along the emergency exit route, there were three live conductors protruding from the 480VAC run of conduit, thereby exposing employees to an electrical hazard. b. In the southwest corner of the building along the emergency exit route, there was a section of rigid conduit with exposed live wires. The wires had been tucked back into the conduit, but the looped ends of the live wires were still exposed, thereby exposing employees to an electrical hazard.