Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1165746.015
Citation: 01012
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $12,675.00
Current Penalty: $12,675.00
Issuance Date: 01/20/2017
Nr Instances: 12
Nr Exposed: 198
Related Event Code (REC):
Gravity: 10
Report ID: 0418100
Contest Date:
Final Order: 02/17/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/17/2017 | $12,675.00 | Serious | ||
Penalty | Z: Issued | 01/20/2017 | $12,675.00 | Serious |
Text For Citation: 01 Item/Group: 012 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about 7/26/2016 Operators were exposed to potential electrocution hazards where there were unused openings at: a. Line 20, Printer 9, stop button missing, exposing the live electrical parts inside. b. Line 20, Printer 9, rear of panel (2) two unused openings, exposing the live 208V/480V live electrical parts inside. c. Line 19/20 Panel box, missing knockout exposing the 120V/208V live electrical parts inside, operators used the open hole to hang a metal rod use to retrieve stuck products from the lines. d. Line 18 panel box, missing knockout exposing the 120V live electrical parts inside. e. Line 17 unused opening on Square D Start/stop box missing, exposing workers to the live 208V/480V electrical parts inside. f. Line 3 Square D electrical box missing (2) blanks, exposing the live 208V/480V electrical parts inside. g. Line 22 electrical box missing knockout exposing the live 230V electrical parts inside. h.Line 30 tip tray missing (2) two knockouts exposing the live 110V electrical parts inside. i. Line 25A metallic quad outlet missing left side receptacles exposing the live 110V electrical parts inside. j. Line 25, Dayton split phase motor 6XJ35BA, 115V 60Hz installed without being covered at electrical connections and was not connected at the ground. Water was identified within 6 feet of the hazard. k. Line 5 Bagger, trap winder was missing its guard/cover exposing the un-insulated copper wiring and screw caps.