Violation Detail
Standard Cited: 19100333 B02 I Selection and use of work practices
Inspection Nr: 1208858.015
Citation: 01011E
Citation Type: Serious
Abatement Date: 08/04/2017 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/13/2017
Nr Instances: 2
Nr Exposed: 10
Related Event Code (REC): C
Gravity: 10
Report ID: 0521400
Contest Date: 08/07/2017
Final Order: 08/01/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/01/2018 | $0.00 | 08/04/2017 | Serious | |
Penalty | C: Contested | 08/08/2017 | $0.00 | 08/04/2017 | Serious | |
Penalty | Z: Issued | 07/13/2017 | $0.00 | 08/04/2017 | Serious |
Text For Citation: 01 Item/Group: 011E Hazard:
29 CFR 1910.333(b)(2)(i): The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives. The employer did not maintain written procedures to ensure parts were de-energized, locked out and tagged in accordance with paragraph (b). a. On or about 16 February 2017 and on dates prior, employees were required to work live on electrical equipment up to 480 volts. Employees were required to use a voltage meter to test a 480 volt motor switch plate. b. On or about 06 March 2017, employees were directed to work in energized 480 volt Motor Control Cabinets (MCCs). Employees were instructed to work inside the cabinets without the adequate lockout procedures for electrical safety needed to safely perform the task. This exposed employee(s) assigned to perform work on up to 480v circuits to electric shock, and electrocution. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).