Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1650860.015
Citation: 01011C
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 08/01/2023
Nr Instances: 3
Nr Exposed: 3
Abatement Date:
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 08/22/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/22/2023 | $0.00 | Serious | ||
Penalty | Z: Issued | 08/01/2023 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 011C Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. a) On or about February 15, 2023, at a workplace located at 210 Maple Street, Denmark, WI in the Main Cutting Department; the flexible electrical cord powering the Baileigh Sander was pulled away from the fitting, exposing the internal conductors. b) On or about February 14, 2023, at a workplace located at 210 Maple Street, Denmark, WI in the Ariens Building; the flexible cord powering the dust collection system disconnect was pulled away from the fitting, exposing the internal conductors. c) On or about February 15, 2023, at a workplace located at 210 Maple Street, Denmark, WI in the CNC Building; the flexible cord powering the Heian vertical milling machine was pulled away from the fitting entering the machine cabinet, exposing the internal conductors.