Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1769330.015
Citation: 01011B
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/10/2025
Nr Instances: 1
Nr Exposed: 14
Abatement Date:
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 03/05/2025
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/05/2025 | $0.00 | Other | ||
Penalty | Z: Issued | 02/10/2025 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 011B Hazard:
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels; and a. On or about September 10, 2024, the working space in front of the electrical circuit breaker panel for Printer #7 was 24 ? inches, which did not permit the panel door to open at least 90-degrees which exposed employees to electrical shock hazards up 480 VAC.