Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1721955.015
Citation: 01011B
Citation Type: Serious
Abatement Date: 08/12/2024 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/18/2024
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 5
Report ID: 0419400
Contest Date: 08/06/2024
Final Order: 11/27/2024
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 11/27/2024 | $0.00 | 08/12/2024 | Serious | |
Penalty | C: Contested | 10/10/2024 | $0.00 | 08/12/2024 | Serious | |
Penalty | Z: Issued | 07/18/2024 | $0.00 | 08/12/2024 | Serious |
Text For Citation: 01 Item/Group: 011B Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Coating mill - On or about January 25, 2024, the employer has electrical panels with multiple breakers at different amps that are not labeled to indicate what breaker energizes what equipment exposing employees to electrical hazards.